Honeywell Vigilon 4 loop Generic Commissioning Instructions page 125

Fire panels & network nodes
Table of Contents

Advertisement

Message
associated with..
Network
End switching normal
at card x
Exception number x on
(Exceptions also referred to
loop y
as Sub-Fault)
Loop Processor Card
LPC
Excessive
transmission error
(loop processor card)
rate
Too many errors: lost
device or loop split
External Fire at
MCC / MCB
panel n
(main control card/board)
Device
FARE Enabled /
Disabled
number z on
loop y Zone x
FARE Activated /
Device
Deactivated
number z on loop y
zone x
Device
FARE Faulty/Restored
number x loop y
zone w
Device
FARE loop x, device y
Fast scan started
Data logging
number x on loop y
channel z
MCC / MCB
Fault cleared Warning
(main control card/board)
cleared
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
meaning..
Network card is back to normal operation, (see also
end switching disabled)
Change noted in the environment of the device
There were more than 10 reply errors in one day.
(More than 16 reply errors will cause the device
isolation.)
There is a Fire on another panel in a network.
The FARE device has been enabled or disabled
manually or automatically.
The FARE device has been activated / deactivated
manually or automatically.
A 'faulty' message is given when there is a fault
associated with FARE equipment.
This information shows the FARE Interface is on
loop x and is device y.
Fire sensor has detected a change on its input.
Fault or warning has now gone.
..possible action
-
Check the condition codes.
Check screening and electrical noise in area of
operation + check loose connections to loop.
Investigate the fire.
Manually enable or disable the FARE device if
required.
If appropriate manually deactivate the FARE
device. The deactivation happens automatically
on resetting the system after a fire event.
A 'restored' message is given when the FARE
equipment fault is investigated and rectified.
-
The message is normally given when the data
logger is connected.
-