Honeywell Vigilon 4 loop Generic Commissioning Instructions page 119

Fire panels & network nodes
Table of Contents

Advertisement

Message
associated with..
LPC
ASCII Device is
faulty number x on
(loop processor card)
loop y
NVM
Back up
(non volatile memory) on
backplane or MCB
Back up required
NVM
(non volatile memory) on
backplane or MCB
Power supply
Battery discharged
Battery disconnected/
Power supply
restored
MCC / MCB / Network Card
Baud rate x at card y
being Initialised at
NVM
card x
(non volatile memory) on
backplane or MCB
Any Card
Buffer full at card x
Any Card
Buffers out of step
at card x
Device
Call point glass is
broken
number x loop y
Device
Call point on
interface unit
operated / restored
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
meaning..
Failure of the Control panel to communicate with
Repeat / Mimic panel. The power supplies to these
panels may not be connected.
Data is being copied from cards and stored onto the
NVM.
Data must be saved to memory
This indicates the failure of battery load test. The ADC
value should be equal to or less than normal - 9.
A disconnection is indicated when the ADC value from
the battery is equal to or less than 130.
Baud rate set has been read.
Memory is being set up by the MCC / MCB (main
control card/board), ready for use.
Software error.
Software error.
Call point has been operated when the device is
disabled.
Mains powered interface input has been triggered by
conventional MCP, value of input is equal to or less
than 6V.
..possible action
If applicable, connect the power supply or
RESET the Master Repeat Card in the Repeat
and Mimic panel. If necessary replace the
card/software.
-
Back up data to the memory.
Check load test and the battery condition.
Normally it should be = 234 (27.4V)
To give a restored indication the ADC value
should = Vbatt 1/6x256/5.
If required, change the baud rate.
-
-
Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
Replace the glass, if necessary.
-