associated with..
Any Card
Program not running
at card x
Any Card
Program runaway at
card x
Any Card
Q buffer full at
card x
Q buffer number
Any Card
Failed at card x
Radio devices
LRT
recovered
LPC
Recover failed
at
card x
(loop processor card)
LPC
Recover succeeded at
card x
(loop processor card)
LPC
Replaced Device Wrong
type number x on
(loop processor card)
loop y
LPC
SAFE Address not Set
up number x on loop y
(loop processor card)
LPC
Scan error number x
at card y
(loop processor card)
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loops & Compact (VA) panels & network nodes
meaning..
Problem with software, the watchdog will operate the
MCC / MCB (main control card/board).
CPU has crashed.
Software error.
Software error.
Radio LRT has completed finding all of the radio
devices
Loop does not match with what is in NVM.
Successful recovery after a previous failure.
Device is a different type.
The replaced device is not SAFE addressed. The
device previously installed in the location was SAFE
addressed.
Invalid universal scan reply.
..possible action
Software errors will activate an automatic
system reset.
Ignore for single occurrence.
Record event in the log book.
Clear and ignore single occurrence. Record in
the log book.
Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
-
Check and confirm/correct the difference and
then backup.
-
Check and confirm installation of correct type
and reallocate. Back up to memory.
Set up the SAFE address.
Check loop length and screening