Beam sensor STATES

States verses distance
Sensor STATES
Ideal range
minimum to maximum
4 or 5
2m to 30m
2 or 3
5m to 100m
0 or 1
12m to 100m
State
Definition
Default
State 0#
detection
State 1
Normal
sensitivity
State 2
Medium
Sensitivity
State 3
Medium
Sensitivity
State 4
High Sensitivity
State 5
High Sensitivity
State 15
No detection.
# - factory default STATE
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Application
A fire is detected when there is a 50% (3dB) fall in signal level, however if the fall is by 90% (10dB) in less than
1second and is maintained for 40 seconds, then a fault is registered. This allows the Control panel to differentiate
between a fire and a fault signal caused by accidental obscuration.
A fire is detected when there is a 50% (3dB) fall in signal level, however if the fall is by 90% (10dB) in less than
1 second and is maintained for 40 seconds then a fire is registered.
A fire is detected when there is a 25% (1.3dB) fall in signal level, however if the fall is by 90% (10dB) in less than
1 second and is maintained for 40 seconds then a fault is registered.
A fire is detected when there is a 25% (1.3dB) fall in signal level, however if the fall is by 90% (10dB) in less than
1 second and is maintained for 40 seconds then a fire is registered.
A fire is detected when there is a 10% (0.5dB) fall in signal level, however if the fall is by 90% (10dB) in less than
1 second and is maintained for 40 seconds then a fault is registered.
A fire is detected when there is a 10% (0.5dB) fall in signal level, however if the fall is by 90% (10dB) in less than
1 second and is maintained for 40 seconds then a fire is also registered.
This is a total disablement of the sensor.