Integral Sounder Operation - Honeywell Vigilon 4 loop Generic Commissioning Instructions

Fire panels & network nodes
Table of Contents

Advertisement

Commissioning instructions

Integral sounder operation

A sensor sounder device can have its integral sounder only actioned in the event of a local fire event being detected at the device.
¨
Integral sounder Sector operation (sometimes also called 'flag set' Sector) can be configured using the panel menu commands [SetUp]-> [Sector] -> [Sounder] -> [On]
¨
when a Sector is configured for 'integral sounder mode' then a fire event from a sensor sounder in the Sector will cause only the integral sounder to operate
¨
linked Sectors are not affected when sensor/sounder type device is triggered from Sector configured for 'integral operation mode', only its local sounder operates and fire is
reported at the panel
¨
Delay Blocks can be configured to action other Sectors from sector operating in an integral sounder mode
¨
Sectors configured for integral sounder mode operation can be setup to action command builds.
SECTOR X
Sensor
Alarm
device
FIRE
Setup
H
MCP
INTERFACE
144
SECTOR X
OPERATION
Sensor
Alarm
SECTOR X
device
INTEGRAL
FLAG SET
SOUNDER - ON
ON
H
MCP
INTEGRAL
SOUNDER
FLAG
OFF
SET OFF
DEFAULT
(DEFAULT)
The
sector x
actioned by another sector.
NOTE: OTHER SENSOR SOUNDERS
IN AN `INTEGRAL SOUNDER SECTOR'
OPERATE IN A SIMILAR MANNER
ONLY LOCAL
ALARM SOUNDS
FIRE
COMMAND
ACTION
BUILD
ACTION
DELAY
BLOCK
ACTION
SECTOR
INTERFACE
This action is only applicable
if the
fire
was from a
Sensor Alarm device
will operate normally when
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.