Power Specifications; Estimating Power Requirements - Cisco ASR 5000 Series Installation Manual

Hide thumbs Also See for ASR 5000 Series:
Table of Contents

Advertisement

▀ Power Specifications

Power Specifications
The following table provides essential power specifications for the chassis and all associated cards within the system.
Table 87.
Chassis Power Requirements
Characteristic
Input Voltage
TUV Rated Peak Current Load
Maximum Peak Power Load
Chassis Maximum Power Load
Line Card (rear-installed) Maximum Power Load
Application Card (front-installed) Maximum Power Load

Estimating Power Requirements

Use the following formula to estimate total power consumption for each deployed chassis.
(Total Application Card Maximum Power Load) + (Total Line Card Maximum Power Load) + (Chassis Maximum
Power Load)
For example, the calculation for estimating the power required for an ASR 5000 installation with (3) PSC2s, (2) SMCs,
(2) SPIOs, (2) RCCs, and (4) GLC2s would be:
(325W x 3) + (130W x 2) + (20W x 2) + (13.5W x 4) + 800W = 2129W
▄ ASR 5000 Installation Guide
260
Value
Maximum range: -40VDC to -60VDC
Nominal range: -48VDC to -60 VDC
165A @ -48 VDC
5760W
800W
SPIO: 15W
FLC2: 13.5W
GLC2: 10.5W
QGLC: 15W
XGLC: 25W
OLC2:23W
CLC2: 23W
RCC: 20W
SMC: 130W
PSC2: 325W
PSC3: 330W
Technical Specifications