Cisco ASR 5000 Series Installation Manual page 120

Hide thumbs Also See for ASR 5000 Series:
Table of Contents

Advertisement

▀ Connecting to the CO Alarm Interface
The 8-foot (2.4 meter) CO alarm cable shipped with the chassis supports redundant SPIO card installations. This "Y"
cable has two Molex connectors on one end that are keyed to fit into the CO Alarm interfaces in one direction only.
Each connector mates with one of the side-by-side SPIO cards. On the opposite end is a 9-pin terminal block that you
can mount to the telco cabinet or equipment rack frame.
The following figure and table display this cable assembly and its pinouts.
Figure 39.
Table 38.
SPIO CO Alarms Cable Assembly Pinout
SPIO CO Alarms IF Pin Number
1
2
3
4
5
6
7
8
9
10
▄ ASR 5000 Installation Guide
120
SPIO CO Alarms Cable Assembly
Cable Wire Color
Black
Orange
Red
Brown
Yellow
Green
Blue
Violet
Gray
Not wired
Terminal Block Position No.
1
2
3
4
5
6
7
8
9
Not equipped
Cabling the Switch Processor Input/Output Line Card
Signal
Major Alarm - Normally closed
Major Alarm - Common
Major Alarm - Normally open
Minor Alarm - Normally closed
Minor Alarm - Common
Minor Alarm - Normally open
Critical Alarm - Normally closed
Critical Alarm - Common
Critical Alarm - Normally open
Unused

Advertisement