▀ Interface Specifications
Figure 64.
Table 95.
CO Alarms Cable Pinout
CO Alarms IF Pin No.
1
2
3
4
5
6
7
8
9
10
Electrical Characteristics
Each of the three dry-contact relay switches is rated to support a maximum switching current of 1A@30VDC. The relay
contacts should not directly connected to high current devices such as sirens and flashing lamps.
▄ ASR 5000 Installation Guide
268
SPIO CO Alarms Cable Assembly
Cable Wire Color
Cable Terminal Block Position No.
Black
1
Orange
2
Red
3
Brown
4
Yellow
5
Green
6
Blue
7
Violet
8
Gray
9
Not wired
Not equipped
Technical Specifications
Signal
Major Alarm - Normally closed
Major Alarm - Common
Major Alarm - Normally open
Minor Alarm - Normally closed
Minor Alarm - Common
Minor Alarm - Normally open
Critical Alarm - Normally closed
Critical Alarm - Common
Critical Alarm - Normally open