Error
Error
Error name
code
(System/
(Hexad
axis/axes
ecimal)
group)
341DH
System
Out of Input Absolute
Coordinate Range
341EH
System
Out of Output Absolute
Coordinate Range
341FH
System
Out of Composite Mode
Range
3421H
System
Out of Input Offset
Range
3422H
System
Out of Output Offset
Range
3423H
System
Out of Input Coefficient
Range
3424H
System
Out of Output
Coefficient Range
342DH
System
SD Memory Card Use
Disabled
342EH
System
SD Memory Card Write
Disabled
342FH
System
SD Memory Card
Unload
3430H
System
SD Memory Card Error
3433H
System
Out of Request ID
Setting Value Range
3434H
System
Request Data Setting
Value Incorrect
3435H
System
Out of Request Data
Setting Value Range
3436H
System
Out of Response Data
Length Setting Value
Range
Error detail and cause
Detection
timing (At
start/
during
control
The value is out of range for
When
InputAbsolute.
executing FB
The value is out of range for
When
OutputAbsolute.
executing FB
The value is out of range for
When
SynthesizingMode.
executing FB
The value is out of range for
When
InputOffset.
executing FB
The value is out of range for
When
OutputOffset.
executing FB
The value is out of range for
When
InputScaling.
executing FB
The value is out of range for
When
OutputScaling.
executing FB
SD memory card is not mounted.
When
Or it was wrote to SD memory
accessing SD
card when
memory card
"System.Md.SdcForcedDisable
(SD memory card forced Stop
using status flag)" is TRUE.
It was wrote to SD memory card
When
when SD memory card is
accessing SD
"System.Md.SdcProtect (SD
memory card
memory card protect flag)" is
TRUE.
The memory card was removed
When
without SD memory card being
removing SD
disabled.
memory card
SD memory card is corrupted
When
accessing SD
memory card
The value is out of range for
When
Request ID.
executing
dedicated
instruction
Incorrect request data is set.
When
executing
dedicated
instruction
The value is out of range for
When
request data length.
executing
dedicated
instruction
The value is out of range for
When
response data length.
executing
dedicated
instruction
Operation at
Remedy
error
occurrence
Not execute FB.
Set the value within the
range.
Not execute FB.
Set the value within the
range.
Not execute FB.
Set the value within the
range.
Not execute FB.
Set the value within the
range.
Not execute FB.
Set the value within the
range.
Not execute FB.
Set the value within the
range.
Not execute FB.
Set the value within the
range.
The access is not
• Format SD Memory
allowed.
Card.
• Remount SD Memory
Card.
• Replace SD Memory
Card.
• Disable the write-
protected switch and
remount.
The access is not
Change SD Memory
allowed.
Card protect flag to
FALSE.
Remove SD memory
card after SD memory
card being disabled.
The access is not
• Format SD Memory
allowed.
Card.
• Remount SD Memory
Card.
• Replace SD Memory
Card.
Dedicated instruction is
Check setting data.
completed with the error.
Dedicated instruction is
Check setting data.
completed with the error.
Dedicated instruction is
Check setting data.
completed with the error.
Dedicated instruction is
Check setting data.
completed with the error.
22 TROUBLESHOOTING
22.5 List of Error Codes
22
553