GE AF-650 GP Programming Manual page 41

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
F-52 Minimum Reference
Range:
3
3
F-53 Maximum Reference
Range:
1500.000
ReferenceFeed-
backUnit
*
F-54 Reference Function
Option:
[0]
Sum
*
[1]
External/Preset Use either the preset or the external
3.3.8 F-6# References
Parameters to configure drive to add or subtract a fixed
value to an input reference.
F-62 Catch up/slow Down Value
Range:
0 %
[0 -
*
100 %]
40
AF-650 GP Programming Guide
Function:
closed loop, RPM;
for [2] Torque, Nm.
The unit selected
in F-51 Reference/
Feedback Unit.
Function:
[par. F-52 -
Enter the Maximum
999999.999
Reference. The Maximum
ReferenceFeed-
Reference is the highest
backUnit]
value obtainable by
summing all references.
The Maximum Reference
unit matches:
The choice of
configuration in
H-40 Configuration
Mode: for [1] Speed
closed loop, RPM;
for [2] Torque, Nm.
The unit selected
in F-50 Reference
Range.
Function:
Sums both external and preset reference
sources.
reference source.
Shift between external and preset via a
command or a digital input.
Function:
Enter a percentage (relative) value to be either
added to or deducted from the actual reference
for Catch up or Slow down respectively. If Catch
up is selected via one of the digital inputs
(E-01 Terminal 18 Digital Input to E-06 Terminal 33
Digital Input), the percentage (relative) value is
added to the total reference. If Slow down is
selected via one of the digital inputs
(E-01 Terminal 18 Digital Input to E-06 Terminal 33
Digital Input), the percentage (relative) value is
deducted from the total reference. Obtain
F-62 Catch up/slow Down Value
Range:
Function:
extended functionality with the DigiPot function.
See parameter group F-9# Digital Pot-Meter.
F-64 Preset Relative Reference
Range:
Function:
0 %
[-100 -
The actual reference, X, is increased or
*
100 %]
decreased with the percentage Y, set in
F-64 Preset Relative Reference. This results in the
actual reference Z. Actual reference (X) is the
sum of the inputs selected in F-01 Frequency
Setting 1, C-30 Frequency Command 2,
C-34 Frequency Command 3 and O-02 Control
Word Source.
Illustration 3.12 Preset Relative Reference
Illustration 3.13 Actual Reference
F-68 Relative Scaling Reference Resource
Option:
Function:
NOTE
This parameter cannot be adjusted
while the motor is running.
Select a variable value to be added to the
fixed value (defined in F-64 Preset Relative
Reference). The sum of the fixed and
variable values (labelled Y in
Illustration 3.14) is multiplied with the actual
reference (labelled X in Illustration 3.14).
This product is then added to the actual
reference (X+X*Y/100) to give the resultant
actual reference.