GE AF-650 GP Programming Manual page 122

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
LC-02 Stop Event
Select the boolean (TRUE or FALSE) input to deactivate Logic
Controller.
Option:
[74]
Logic Controller Time-out 7 Logic Controller timer 7 is
[75]
Start command given
[76]
Digital input x30 2
[77]
Digital input x30 3
[78]
Digital input x30 4
[94]
RS Flipflop 0
[95]
RS Flipflop 1
[96]
RS Flipflop 2
[97]
RS Flipflop 3
[98]
RS Flipflop 4
[99]
RS Flipflop 5
[100] RS Flipflop 6
[101] RS Flipflop 7
LC-03 Reset Logic Controller
Option:
Function:
[0]
Do not reset Logic
Retains programmed settings in all
*
Controller
parameter group LC-## Logic
Controller.
[1]
Reset Logic
Resets all parameters in parameter
Controller
group LC-## Logic Controller to default
settings.
3.19.2 LC-1# Comparators
Parameters to configure the Logic Controller (LC)
comparators. Comparators are used for comparing
variables with fixed preset values.
LC-10 Comparator Operand
Array [6]
Option:
Function:
Choices [1] to [31] are variables which
will be compared based on their
values. Choices [50] to [186] are digital
values (TRUE/FALSE) where the
comparison is based on the amount
of time during which they are set to
AF-650 GP Programming Guide
Function:
timed out.
See parameter group LC-1#
Comparators
See parameter group LC-1#
Comparators
See parameter group LC-1#
Comparators
See parameter group LC-1#
Comparators
See parameter group LC-1#
Comparators
See parameter group LC-1#
Comparators
See parameter group LC-1#
Comparators
See parameter group LC-1#
Comparators
DET-618C
LC-10 Comparator Operand
Array [6]
Option:
Function:
TRUE or FALSE, respectively. See
LC-11 Comparator Operator.
Select the variable to be monitored by
the comparator.
[0]
DISABLED
The comparator is disabled.
*
[1]
Reference
The resulting remote reference (not
local) as a percentage.
[2]
Feedback
In the unit [RPM] or [Hz]
[3]
Motor speed
[RPM] or [Hz]
[4]
Motor Current
[A]
[5]
Motor torque
[Nm]
[6]
Motor power
[kW] or [hp]
[7]
Motor Rated
[V]
Voltage
[8]
DC-link voltage
[V]
[9]
Motor Thermal
Expressed as a percentage.
[10]
Drive thermal
Expressed as a percentage.
[11]
Heat sink temp.
Expressed as a percentage.
[12]
Analog input AI53
Expressed as a percentage.
[13]
Analog input AI54
Expressed as a percentage.
[14]
Analog input
[V]. AIFB10 is internal 10 V supply.
AIFB10
[15]
Analog input
[V] Analog input AICCT [17] [°]. AIS24V
AIS24V
is switch mode power supply: SMPS
24V.
[17]
Analog input
[°]. AICCT is control card temperature.
AICCT
[18]
Pulse input FI29
Expressed as a percentage.
[19]
Pulse input FI33
Expressed as a percentage.
[20]
Alarm number
The error number.
[21]
Warning number
[22]
Analog input x30
11
[23]
Analog input x30
12
[30]
Counter A
Number of counts
[31]
Counter B
Number of counts
[50]
FALSE
Enters the fixed value of false in the
comparator.
[51]
TRUE
Enters the fixed value of true in the
comparator.
[52]
Control ready
The control board receives supply
voltage
3
3
121