Parameter Descriptions
AN-50 Terminal 42 Output
Option:
Function:
Current, then the setting of AN-52 Terminal 42
Output Max Scale must be:
Imotor x 100%/Imax = 22 A x 100%/38.4 A =
57%
[104] Torque rel
The torque setting is related to setting in
to limit
F-40 Torque Limiter (Driving)
[105] Torq relate
The torque is related to the motor torque
to rated
setting.
[106] Power
Taken from P-07 Motor Power [kW].
[107] Speed
Taken from F-53 Maximum Reference. 20 mA =
value in F-53 Maximum Reference
[108] Torque
Torque reference related to 160% torque.
[109] Max Out
0 Hz = 0 mA,F-03 Max Output Frequency 1 =
Freq
20 mA.
[113] PID
Clamped
Output
[119] Torque %
Torque% lim: Torque reference. F-50 Reference
lim
Range [Min - Max] 0% = 0 mA; 100% = 20 mA
F-50 Reference Range [-Max - Max] -100% = 0
mA; 0% = 10 mA; +100% = 20 mA
[130] Output
0 Hz = 4 mA, 100 Hz = 20 mA
freq.
4-20mA
[131] Reference
F-50 Reference Range [Min-Max] 0% = 4 mA;
4-20mA
100% = 20 mA
F-50 Reference Range [-Max-Max] -100% = 4
mA; 0% = 12 mA; +100% = 20 mA
[132] Feedback
Feedback 4-20 mA: F-50 Reference Range [Min-
4-20mA
Max] 0% = 4 mA; 100% = 20 mA
F-50 Reference Range [-Max-Max] -100% = 4
mA; 0% = 12 mA; +100% = 20 mA
[133] Motor cur.
Value is taken from DR-37 Drive Max. Current.
4-20mA
Inverter max. current (160% current) is equal
to 20 mA.
[134] Torq.% lim
The torque setting is related to setting in
4-20 mA
F-40 Torque Limiter (Driving).
[135] Torq.%
The torque setting is related to the motor
nom
torque setting.
4-20mA
[136] Power
Taken from P-07 Motor Power [kW]
4-20mA
[137] Speed
Taken from F-53 Maximum Reference. 20 mA =
4-20mA
Value in F-53 Maximum Reference.
[138] Torque
Torque reference related to 160% torque.
4-20mA
[139] Bus ctrl.
An output value set from Network process
0-20 mA
data. The output will work independently of
internal functions in the frequency converter.
AF-650 GP Programming Guide
AN-50 Terminal 42 Output
Option:
[140] Bus ctrl.
4-20 mA
[141] Bus ctrl
0-20mA t.o.
[142] Bus ctrl
4-20mA t.o.
[149] Torque %
lim 4-20mA
[150] Max Out Fr
4-20mA
AN-51 Terminal 42 Output Min Scale
Range:
0 %
*
%]
AN-52 Terminal 42 Output Max Scale
Range:
100
%
*
DET-618C
Function:
An output value set from Network process
data. The output will work independently of
internal functions in the frequency converter.
H-74 Warning Reference Low defines the
behaviour of the analog output in case of bus
time-out.
H-74 Warning Reference Low defines the
behaviour of the analog output in case of bus
time-out.
Analog output at zero torque = 12 mA.
Motoric torque will increase the output
current to max torque limit 20 mA (set in
F-40 Torque Limiter (Driving)).
Generative torque will decrease the output to
torque limit Generator Mode (set in
F-41 Torque Limiter (Braking))
Ex: F-40 Torque Limiter (Driving): 200% and
F-41 Torque Limiter (Braking): 200%. 20 mA =
200% Motoric and 4 mA = 200% Generatoric.
Illustration 3.33
0 Hz = 0 mA, F-03 Max Output Frequency 1 =
20 mA.
Function:
[0 - 200
Scale for the minimum output (0 or 4 mA) of
the analog signal at terminal 42.
Set the value to be the percentage of the full
range of the variable selected in
AN-50 Terminal 42 Output.
Function:
[0 -
Scale the maximum output of the selected
200 %]
analog signal at terminal 42. Set the value to
the maximum value of the current signal output.
Scale the output to give a current lower than 20
mA at full scale; or 20 mA at an output below
100% of the maximum signal value. If 20 mA is
the desired output current at a value between 0
- 100% of the full-scale output, program the
percentage value in the parameter, i.e. 50% = 20
mA. If a current between 4 and 20 mA is desired
at maximum output (100%), calculate the
percentage value as follows: