GE AF-650 GP Programming Manual page 127

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
LC-43 Logic Rule Operator 2
Array [6]
Option:
3
3
[0]
DISABLED
*
[1]
AND
[2]
OR
[3]
AND NOT
[4]
OR NOT
[5]
NOT AND
[6]
NOT OR
[7]
NOT AND NOT
[8]
NOT OR NOT
LC-44 Logic Rule Boolean 3
Array [6]
Option:
Function:
[0]
False Select the third boolean (TRUE or FALSE) input for
*
the selected logic rule. See LC-01 Start Event ([0] -
[61]) and LC-02 Stop Event ([70] - [75]) for further
description.
3.19.5 LC-5# States
Parameters to configure the Logic Controller (LC) states.
States define the events and actions to take place in the
drive.
LC-51 Logic Controller Event
Array [20]
Option:
Function:
[0]
False Select the boolean input (TRUE or FALSE) to define
*
the Logic Controller event.See LC-01 Start Event ([0] -
[61]) and LC-02 Stop Event ([70] - [74]) for further
description.
LC-52 Logic Controller Action
Array [20]
Option:
[0]
DISABLED
*
126
AF-650 GP Programming Guide
Function:
Select the second logical operator to be
used on the boolean input calculated in
LC-40 Logic Rule Boolean 1, LC-41 Logic Rule
Operator 1, and LC-42 Logic Rule Boolean 2,
and the boolean input coming from
LC-42 Logic Rule Boolean 2.
[LC-44] signifies the boolean input of
LC-44 Logic Rule Boolean 3.
[LC-40/LC-42] signifies the boolean input
calculated in LC-40 Logic Rule Boolean 1,
LC-41 Logic Rule Operator 1, and LC-42 Logic
Rule Boolean 2. [0] DISABLED (factory
setting). select this option to ignore
LC-44 Logic Rule Boolean 3.
Function:
Select the action corresponding to the LC
event. Actions are executed when the
corresponding event (defined in
LC-52 Logic Controller Action
Array [20]
Option:
Function:
LC-51 Logic Controller Event) is evaluated
as true. The following actions are
available for selection:
[0] *DISABLED
[1]
No action
[2]
Select set-up 1
Changes the active set-up (K-10 Active
Set-up) to '1'.
If the set-up is changed, it will merge
with other set-up commands coming
from either the digital inputs or via a
Network.
[3]
Select set-up 2
Changes the active set-up K-10 Active Set-
up) to '2'.
If the set-up is changed, it will merge
with other set-up commands coming
from either the digital inputs or via a
Network.
[4]
Select set-up 3
Changes the active set-up (K-10 Active
Set-up) to '3'.
If the set-up is changed, it will merge
with other set-up commands coming
from either the digital inputs or via a
Network.
[5]
Select set-up 4
Changes the active set-up (K-10 Active
Set-up) to '4'.
If the set-up is changed, it will merge
with other set-up commands coming
from either the digital inputs or via a
Network.
[10] Select preset ref
Selects preset reference 0.
0
If the active preset reference is changed,
it will merge with other preset reference
commands coming from either the digital
inputs or via a Network.
[11] Select preset ref
Selects preset reference 1.
1
If the active preset reference is changed,
it will merge with other preset reference
commands coming from either the digital
inputs or via a Network.
[12] Select preset ref
Selects preset reference 2.
2
If the active preset reference is changed,
it will merge with other preset reference
commands coming from either the digital
inputs or via a Network.
[13] Select preset ref
Selects preset reference 3.
3
If the active preset reference is changed,
it will merge with other preset reference
commands coming from either the digital
inputs or via a Network.
DET-618C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents