Introduction
1.6.3 Pulse Start/Stop
Terminal 18 = E-01 Terminal 18 Digital Input Latched start,
[9]
Terminal 27= E-03 Terminal 27 Digital Input Stop inverse, [6]
Terminal 37 = Safe stop (where available)
Illustration 1.7 Pulse Start/Stop
1.6.4 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = E-01 Terminal 18 Digital Input Start
[9] (default)
Terminal 27 = E-03 Terminal 27 Digital Input
Freeze reference [19]
Terminal 29 = E-04 Terminal 29 Digital Input
Speed up [21]
Terminal 32 = E-05 Terminal 32 Digital Input
Speed down [22]
Illustration 1.8 Speed Up/Down
AF-650 GP Programming Guide
1.6.5 Potentiometer Reference
Voltage reference via a potentiometer
Illustration 1.9 Potentiometer Reference
DET-618C
Reference Source 1 = [1] Analog input 53 (default)
Terminal 53, Low Voltage = 0 V
Terminal 53, High Voltage = 10 V
Terminal 53, Low Ref./Feedback = 0 RPM
Terminal 53, High Ref./Feedback = 1500 RPM
Switch S201 = OFF (U)