5 Control system
5.2 Safety protection and control
Compressor protection
The compressor is protected by the following devices:
•
High pressure switch: this stops the compressor when the discharge pressure exceeds the set value.
•
Oil heater: this prevents oil from being lost during cold starts, as it is enabled while the compressor is at a standstill.
Fan motor protection: internal thermostat located in the fan motor winding. This stops the fan motor when the winding
•
temperature exceeds the set value.
Setting control and safety devices for indoor units
Model
Switch
For the evaporator
off
fan motor: internal
Switch
thermostat
on
For the control circuit:
-
fuse capacity
For the evaporator
fan motor: internal
thermostat
For the control
circuit: fuse capacity
201
SMGB0077 rev.0 - 01/2013
RCI-(1.0-3.0)FSN3
ºC
100±4
ºC
90±4
A
5
Model
RPC
Switch
ºC
135±5
off
Switch
ºC
90±15
on
-
A
5
RCI-(4.0-6.0)FSN3
RCI-FSN3Ei
100
/
145±5
+15
-10
100
/
90±15
+15
-10
5
5
RPI(M)
RPK
-
130±5
-
83±15
6,3
5
RCIM-FSN2
RCD
145±5
130±5
90±15
83±15
5
5
RPF(I)
130±5
93±15
5
5