3 Piping work and
refrigerant charge
Consider the following sizes: a + b + c ≤ 780 mm.
C A U T I O N
Do not apply adhesive between the drain hose connection and the drain hose.
Do not apply too much force when making the drain hose connection as this could damage it.
Do not use bent or twisted drain pipes as these will cause water leaks.
Then insulate the drain hose appropriately.

3.5.4 RCD - 2-way cassette (1.0-5.0)FSN2


Refrigerant pipe installation
The correct position for the refrigerant pipe connection is shown
below. The pipe connection must be accessible from all directions
(above, left or right).
Models
RCD-(1.0/1.5)FSN2
RCD-2.0FSN2
RCD-(2.5–5.0)FSN2
107
SMGB0077 rev.0 - 01/2013
Drainage pipe
connection
(1) Gas pipe mm (inches)
Ø12.70 (1/2)
Ø15.88 (5/8)
Clamp (accessory)
Do not use adhesive
4% (1/25) - 1% (1/100)
Drain pipe (accessory)
Clamp (accessory)
Do not use adhesive
PVC pipe Ø 32
(field-supplied)
Use PVC adhesive
Drainage pipe
(accessory)
(2) Liquid pipe mm (inches)
Ø6.35 (1/4)
Ø9.52 (3/8)
3