Removing Electronic Expansion Valve Coil - Hitachi RCI-1.0FSN3 Service Manual

Indoor units system free series & complementary systems fsn(h)(2/3/4)(e/m)(i)(-du)
Table of Contents

Advertisement

10 Servicing

10.1.11 Removing Electronic Expansion Valve Coil

C A U T I O N
TURN OFF all power source switches.
1 Remove the air panel according to the item "Removing Optional Air Panel".
2 Remove the bell-mouth according to the item "Removing Turbo Fan and Fan Motor".
3 Remove the drain pan according to the item "Removing Drain Pan".
4 Remove the partition plate according to the item "Removing Thermistors for Liquid Pipe and Gas Pipe".
Fixing Plate
for Thermistor
Expansion Valve
Coil
Hook
Expansion Valve
Body
Projection
5 Cut the plastic band fixing lead wires (for 2 pipe thermistors and expansion valve).
6 Remove the hooks of the expansion valve coil from the projection of the expansion valve body by a few turn of
expansion valve coil. Pull up and remove the expansion valve coil. At this time, pay attention not to twist the pipes.
7 Insert the new expansion valve coil for replacement to the expansion valve body. When inserting, fix the expansion
valve coil to catch the projections onto the hooks.
N O T E
The hooks are located each 90o, and the projections are located each 180o.
The hooks shall catch onto the projections completely though the rotation direction does not affect to the operation.
If the hooks do not completely catch onto the projections, it may cause malfunction of expansion valve coil.
8 If the replacement work is completed, fix the wire for expansion valve near the expansion valve coil by plastic band. At
this time, fix the lead wires for expansion valve to face the edge downward.
After fixing the lead wires for expansion valve, fix again lead wires (for 2 pipe thermistors and the expansion valve)
together by the plastic band.
N O T E
When reassembling, securely fix lead wires (for fan motor, 2 pipe thermistors and expansion valve) together by
the cord clamp attaching at the partition plate.
313
SMGB0077 rev.0 - 01/2013
Expansion Valve
Wire for Expansion Valve
Thermistor
for Gas Pipe
Plastic Band
Thermistor
for Liquid Pipe
Plastic Band
Fix the lead wires for expansion
valve by plastic band to
face the edge downward.
Liquid Pipe
The rotation direction does not
affect to the operation.
(However, pay attention not to
touch the pipe, plate and drain pan.)
Installation of Drive Part
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents