10 Servicing

10.8.3 Outlet air thermistor

1
Outlet thermistor
N O T E
The thermistor is located on the outlet side of the unit.
To disconnect and remove the appropriate thermistor,
previously see the chapter corresponding to the wiring
diagrams in this Manual.
Disconnect and remove the thermistor.
Removal of the thermistors from the liquid and gas pipes
1
Screws
N O T E
To disconnect and remove the appropriate thermistor,
previously see the chapter corresponding to the wiring
diagrams in this Manual.
Cover the thermistors with cork tape or pipe insulation,
depending on the location. Both materials are factory-
supplied. Replace them if damaged during maintenance
work.
Remove the electrical box cover.
Remove the service cover.
The liquid and gas pipe thermistors are secured to the copper
piping by a special clamp.
Liquid pipe thermistor: covered with cork tape.
Gas pipe thermistor: covered with pipe insulation.