3 Piping work and
refrigerant charge
3.5.3 RCIM-4-way cassette (compact) (0.8-2.0)FSN2
Refrigerant pipe installation
The correct position for the gas refrigerant pipe connection is
shown below. The pipe connection must be accessible from all
directions (above, left or right).
Models
RCIM-(0.8-1.5)FSN2E
RCIM-2.0FSN2E
Drain pipe installation
The correct position for the drain hose connection is shown below.
Prepare a polyvinyl chloride (PVC) pipe with an outer diameter of
32 mm.
Secure the pipe with the clamp and adhesive supplied.
The drain hose must have a gradient of 1% (1/100) to 4% (1/25).
106
SMGB0077 rev.0 - 01/2013
(1) Gas pipe mm (inches)
Ø12.70 (1/2)
Ø15.88 (5/8)
(2) Liquid pipe mm (inches)
Ø6.35 (1/4)
Drain pipe connection