5 Control system
Safety protection and control
5.2 Safety protection and control
Compressor and fan motor protections
The following devices and their combinations protect the compressor and fan motor.
High-pressure switch
This switch cuts out the operation of the compressor when the discharge pressure exceeds the setting.
This band heater protects against the oil carry-over during the cold starting, as the band heater is
Oil heater
energized while the compressor is stopped.
Internal thermostat that is embedded in the fan motor winding: this internal thermostat cuts out the
Fan motor protection
operation of the fan motor when the temperature of the fan motor winding exceeds the setting.
RASC safety and control device setting
Model
High pressure switch for
compressor
Fuse
3N~ 400V 50Hz
Crankcase heater
CCP Timer
Setting Time
Fan Motor Fuse
Internal Thermostat for fan
motor
Fuse capacity on PCB
79
SMGB0091 rev.2 - 11/2015
Type
Automatic Reset, Non-Adjustable (each one for each compressor)
Cut-Out
MPa
Cut-In
MPa
A
Output
W
-
min.
A
Cut-Out
ºC
Cut-In
ºC
A
RASC(4-6)HNPE
-0.05
4.15
-0.15
+0.15
3.20
-0.15
20 x 2
52.0
Non-Adjustable
3
10 x 2
165 ± 10
130 ± 15
5.0
RASC-(8/10)HNPE
-0.05
4.15
-0.15
+0.15
3.20
-0.15
40 x 2
40.8
3
10 x 2
165 ± 10
130 ± 15
5.0
5