Removing Drain-Up Mechanism - Hitachi RCI-1.0FSN3 Service Manual

Indoor units system free series & complementary systems fsn(h)(2/3/4)(e/m)(i)(-du)
Table of Contents

Advertisement

10 Servicing

10.1.8 Removing Drain-Up Mechanism

1 Remove the drain pan according to the item "Removing Drain Pan".
2 Remove the insulation which attaches the wires for float switch and drain-up mechanism together.
3 Cut the plastic band fixing the wires at the fixing plate for float switch.
4 Cut the hose band for drain hose by nipper, and remove the drain hose from the drain-up mechanism.
5 Remove two (2) fixing screws for drain-up mechanism. When removing, hold the drain-up mechanism by hand in order
not to fall.
6 Remove the drain-up mechanism.
N O T E
When reassembling, wrap up the wires for float switch and drain-up mechanism together by the insulation Fix
securely them to the original position. When attaching the drain pan again, pay attention not to pull the wires
strongly. Otherwise, the insulation attaching at the cabinet may be peeled.
Wiring
Drain Hose
Hose Band
310
SMGB0077 rev.0 - 01/2013
Fixing Screws
Drain-up Mechanism
P
Float Switch
Nut
Fixing Plate for
Float Switch
Plastic Band
View from P
Lead Wires
Screw for
Fixing Plate

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents