10 Servicing
10.3.10 Removal of the float switch
Remove the drain pan as indicated in chapter Removal of the
drain pan.
Remove the screw securing switch securing plate to the drain pan
and remove it.
N O T E
The float switch is located at the rear of the drain pan.
Loosen the resin nut securing the float switch and remove it.
Remove the two screws securing the drain mechanism to remove
the mechanism.
N O T E
•
When refitting, make sure the hook is fitted into the groove
in the drain pan and screw into place.
The torque value of the resin nut is 0.3 - 0.4 Nm. If the
•
torque value is higher, the nut will be damaged.
10.3.11 Removal of the thermistors from the liquid and gas pipes
Remove the optional air panel in line with the instructions given in
chapter Removal of the optional air panel.
Remove the fan duct in line with the instructions given in chapter
Removal of the fan duct and the fan.
Remove the drain pan as indicated in chapter Removal of the
drain pan.
Remove the evaporator partition plate securing the heat exchanger
by removing the five screws.
331
SMGB0077 rev.0 - 01/2013
10