10 Servicing
10.6.3 Removal of the thermistors from the liquid and gas pipes
Nº
1
Electrical box
2
Drain pump
3
Screws
N O T E
To disconnect and remove the appropriate thermistor,
•
previously see the chapter corresponding to the wiring
diagrams in this Manual.
•
Cover the thermistors with cork tape or pipe insulation,
depending on the location. Both materials are factory-
supplied. Replace them if damaged during maintenance
work.
Remove the electrical box cover.
Remove the service cover.
The liquid and gas pipe thermistors are secured to the copper
piping by a special clamp.
•
Liquid pipe thermistor: covered with cork tape.
•
Gas pipe thermistor: covered with pipe insulation.
Nº
1
Location of the thermistor
2
Location of the thermistor
N O T E
Black connector: liquid thermistor.
•
•
Yellow connector: gas thermistor.
10.6.4 Removal of the fan parts
Fan parts: fan motor, fan casing and duct.
350
SMGB0077 rev.0 - 01/2013
Part
Part