8 Troubleshooting
8.2 Electronic expansion valve check procedure
Valve position
Locked fully closed
Locked slightly open
Locked fully open
255
SMGB0077 rev.0 - 01/2013
Electronic expansion valve
Check the temperature of the piping in the heating process. Failu-
re of the temperature to rise indicates a fault.
The following conditions indicate a fault:
•
Where the freeze protection thermistor temperature is
lower than the intake air temperature.
•
Where the unit being inspected stops and other units
continue operating in cooling mode.
8