4 Electrical wiring
Test runs
C A U T I O N
•
Be careful during the test runs, as some of the safety functions remain disabled: the units operate for two
hours without switching off via the thermostat. The three-minute compressor protection is not enabled during
the test.
•
Secure the rubber bushes to the panel using adhesive when the outdoor unit ducts are not used.
The compressor remains at a standstill during forced stoppage.
•
4.1.9 Electrical connection of RPF(I) units
Work prior to the electrical connection
1 Turn off the power supply switches before starting work and fit the appropriate locks and safety warnings.
2 Wait 5 minutes after turning off the power supply switches.
3 Check that the fans on the indoor and outdoor units are at a standstill before starting work.
N O T E
The electrical power for the unit must involve a specific power line, with an exclusive power control switch and
•
residual current breaker, installed in line with local or national safety regulations.
•
Check that the electrical power line has enough capacity to supply the unit. Its length, the cable diameter and
their protection (sleeve or jacket) must be appropriate for the unit.
•
For further information, always consider the current regulations in the country where the unit is to be installed.
C A U T I O N
•
Risk of fire: cables must never touch the refrigerant pipes, printed circuit boards (PCB), sharp edges or elec-
trical components inside the unit to avoid damaging them.
•
Loose connection terminals may lead to cable and terminal overheating. The unit may operate incorrectly,
leading to a risk of fire. Check that the cables are firmly secured to the connection terminals.
Electrical connection
Check that the power supply for the RPF/RPFI indoor unit is 230 V. If not, replace connectors CN on the TF transformers
in the electrical box.
N O T E
For RPF units, the correct wiring is connected from the rear
left side.
N O T E
For RPFI units, the correct wiring is connected from the rear
right side.
148
SMGB0077 rev.0 - 01/2013