3 Piping work and
refrigerant charge
The drain piping must be performed with a down-slope pitch of 1/25 to 1/100.
Do not apply excessive force to the Drain Pipe connection. It could cause a damage.
Do not use a bent or twisted Drain Hose. It will cause water leakage.
Insulate the drain pipe after connecting the drain hose.
3.5.2 RCI - 4-way cassette (1.0-6.0)FSN3Ei
Refrigerant pipe installation
The correct position for the refrigerant pipe connection is shown
below. The pipe connection must be accessible from all directions
(above, left or right).
104
SMGB0077 rev.0 - 01/2013
Ceiling
Hose band
a (Max. 300mm)
(accessory)
Drain hose (accessory)
Insulation (5T x 25 x 500)
(accessory)
Completely wrap up
the transparent area
of the drain pipe end
connection
1 to 1.5m
S u p p o r t
part
c
1/25 to 1/100
Down-slope
(mm)
Insulation (5T x 100 x 200)
(accessory)
Wrap up the drain hose
completely to cover the
hose band.
Hose band (accessory)
1
2
2
1