Rpk - Wall Type (0.8-4.0)Fsn(H)3M - Hitachi RCI-1.0FSN3 Service Manual

Indoor units system free series & complementary systems fsn(h)(2/3/4)(e/m)(i)(-du)
Table of Contents

Advertisement

3 Piping work and
refrigerant charge
Kit installation:
Maximum water head height in case of units with drain pump (-DU
models or units with drain up mechanism kit).

3.5.10 RPK - Wall type (0.8-4.0)FSN(H)3M


Refrigerant pipe installation
Gas pipe connection
The position of the gas pipe connection is possible in all directions (above, left or right).
Model
RPK-(0.8-1.0)FSN(H)3M
RPK–1.5FSN(H)3M
RPK-(2.0-4.0)FSN3M
Liquid pipe connection
Model
RPK-(0.8-1.0)FSN(H)3M
RPK–1.5FSN(H)3M
RPK-(2.0-4.0)FSN3M
120
SMGB0077 rev.0 - 01/2013
Measurements (mm)
a
b
c
g
395
107
288
243
395
107
288
262
480
141
339
471
Measurements (mm)
d
e
f
h
450
107
343
188
450
107
343
207
540
141
399
418
Fan cover 2
Left rear side hole for
Insulation
pipe and wire
Refrigerant
gas pipe
g
a
Left rear side hole for
Insulation
pipe and wire
Refrigerant
liquid pipe
h
d
Drain pump
Drain hose
Drain pan
Fan cover 1
RPIM
1/25~1/100
Indoor unit
Down slope
Exterior contour for
indoor unit
b
For right side piping
c
For rear side piping
Exterior contour for in-
e
door unit
For right side piping
f
For rear side piping