Removal Of The Thermistors From The Liquid And Gas Pipes - Hitachi RCI-1.0FSN3 Service Manual

Indoor units system free series & complementary systems fsn(h)(2/3/4)(e/m)(i)(-du)
Table of Contents

Advertisement

10 Servicing
Check that the drainage hole is not blocked.
RCD-(1.0-3.0)FSN2: remove the two screws securing the
reinforcement plate to the drain pan securing plate.
RCD-(4.0/5.0)FSN2: remove the two screws securing the support
plate to the drain pan securing plate and remove it.
Remove the two drain pan securing plates and remove it.
C A U T I O N
Do not use a sharp tool, such as a screwdriver, to fit the
rubber plug, as this could damage it.

10.4.9 Removal of the thermistors from the liquid and gas pipes

Remove the air inlet grille as indicated in chapter Removal of the
long-lasting filter and the air inlet grille.
Remove the fan duct and the fan as indicated in chapter Removal
of the fan duct and the fan.
Remove the drain pan as indicated in chapter Removal of the
drain pan.
Remove the butyl sheet covering the thermistor. Remove the
plate securing the thermistor to the pipe on which it is located and
remove.
N O T E
The thermistor protection and securing system is the
same on the gas and liquid pipe.
The thermistors are secured with brackets.
339