Unit electrical wiring and connection

3.1.8 Electrical connection of RPF(I) units

Work prior to the electrical connection
1 Turn off the power supply switches before starting work and fit the appropriate locks and safety warnings.
2 Wait 5 minutes after turning off the power supply switches.
3 Check that the fans on the indoor and outdoor units are at a standstill before starting work.
?
N O T E
The electrical power for the unit must involve a specific power line, with an exclusive power control switch and residual current breaker,
installed in line with local or national safety regulations.
Check that the electrical power line has enough capacity to supply the unit. Its length, the cable diameter and their protection (sleeve
or jacket) must be appropriate for the unit.
For further information, always consider the current regulations in the country where the unit is to be installed.
!
C A U T I O N
Risk of fire: cables must never touch the refrigerant pipes, printed circuit boards (PCB), sharp edges or electrical components inside
the unit to avoid damaging them.
Loose connection terminals may lead to cable and terminal overheating. The unit may operate incorrectly, leading to a risk of fire.
Check that the cables are firmly secured to the connection terminals.
Electrical connection
Check that the power supply for the RPF/RPFI indoor unit is 230 V. If not, replace connectors CN on the TF transformers
in the electrical box.
?
N O T E
For RPF units, the correct wiring is connected from the rear left side.
?
N O T E
For RPFI units, the correct wiring is connected from the rear right side.
Open the front and side panels.
?
N O T E
To prevent the screws from falling from the terminal box, do not remove them completely, hold onto the terminal and check that the
screw is secure through the hole in the terminal.
Use the following screws for the terminal box:
- M4 screw for the power supply.
- M3.5 screw for the communication line.
52
SMGB0137 rev.0 - 05/2021
Wiring
Side
cover
Wall
Electrical box
Opening
(rear)
Wiring
Front cover
Wall
Electrical box
Front
cover