WSK-WGI Wireless System Gateway
• The Progress Status column indicates progress status of the selected gateway.
• The No. of Devices Joined column indicates the number of devices that are in the mesh network including the gateway.
• The Total Device Count Expected column indicates the number of devices expected to join including the gateway. This field is
editable. Click in to the field to edit the number of device count expected.
10. Once the expected count of devices have joined the mesh, a message is displayed to show that the Mesh formation is complete and
an option is given to choose to start mesh restructuring immediately or wait for any other devices to join.
11. Start Mesh Restructuring (by either waiting or clicking Start). Once Restructuring is initiated, the progress displays. When Mesh
Restructuring is complete, the following success message is shown. For further operating instructions, refer to Section 2.9,
"Operations".
2.8.4 SLC Configuration
The gateway:
 communicates with the control panel via the SLC.
 is only compatible with Gateway firmware version 2.1 or higher.
 occupies one module SLC address. Set the address using the rotary dials on the gateway prior to installation.
The SLC point uses the following configuration parameters:
Type Code Label: Wireless Gateway
A gateway does not initiate alarms but the point is used for event reporting.
18
Figure 2.14 Completed Mesh Formation Screen
Figure 2.15 Completed Restructuring Screen
4
3
Figure 2.16 Address Rotary Switches
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:G 4/13/2020
6 7
8 9
6 7
8 9
10
5
5
11
4
12
3
13
2
2
1
14
1
0
15
0
ONES
TENS
Configuration and Programming