Installation Wiring
2.9.1 W1 Jumper Block (Master Box/Releasing Solenoid Configuration)
Figure 2.9.1.1 illustrates the W1 jumper block positions for the Master Box/Releasing Solenoid configuration.
Figure 2.9.1.1

2.10 Communication Circuits

2.10.1 S3 Series System Communication Circuits
The RPT-E3-UTP is the network communication circuit for the S3 Series System. It provides a remote inter-
face between the ILI-MB-E3/ILI95-MB-E3, ANX (used for Fire applications only) and the Broadband net-
work. It can also be used with the NGA. Use the following network communication circuits with this system.
RPT-E3-UTP (Repeater Module) provides unshielded, twisted-pair wire.
FML-E3 (Fiber-Optic Multi-Mode) provides the fiber-optic multi-mode 62.5 microns fiber.
FSL-E3 (Fiber-Optic Single-Mode) provides the fiber-optic single-mode 50 microns fiber.
For system assembly and installation wiring terminal designations, refer to the following documents:
- RPT-E3-UTP Installation Instructions, P/N: 9000-0580.
- FML-E3/FSL-E3 Installation Instructions, P/N: LS10046-000GF-E.
You can download these documents from the Gamewell-FCI Website (www.gamewell-fci.com).
2.10.2 RPT-E3-UTP Communication Circuit Specifications
Table 2.10.2.1 lists the RPT-E3-UTP communication circuit specifications.
Circuit Supervision:
If the circuit is power-limited:
Supervisory Current:
Max. voltage, rated current, and frequency
(RS-232 & RS-485) do not require these.
Maximum line impedance or equivalent:
2.10.3 RPT-E3-UTP Installation Wiring Diagram
Figure 2.10.3.1 illustrates the RPT-E3-UTP circuit board diagram.
26
W1 Jumper Block Positions for Master Box/Releasing Solenoid
Requirements
Table 2.10.2.1 RPT-E3-UTP Communication Circuit Specifications
15
16
J4
J6
10
2
FIBER
MODULE #2
SW1
8
8
7
6
J5
5
4
10
3
2
1
1
2
FIBER
MODULE #1
Figure 2.10.3.1 RPT-E3-UTP Circuit Board Diagram
S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
RPT-E3-UTP
Supervised
Class 2 Power-Limited
0.016 amp
0.053 amp
0.017 amp
0.053 amp
40 Ohms
J1
J3
GND
TERM
REF
ON OFF
J10
2
ARCNET
TB4
9
RPT-UTP-PCA REV
1
9
1
PRODUCT
GF
J2
DATE CODE
SUPV
ON OFF
LABEL
DG RST DUP MRC REC
PWR
Communication Circuits
FML-E3
FSL-E3
0.079 amp
0.079 amp
TB3
1
1
TB1
1
LED6
RX2
LED5
RX1
LED4
TX