Fire Alarm - Honeywell NOTIFIER N16 Instruction Manual

Fire alarm control panel
Table of Contents

Advertisement

Fire Alarm

4.5 Fire Alarm
Fire Alarm Event
Produces a steady audible tone
appears in the Header Bar
FIRE ALARM
illuminates in the Alert Bar as a red color indicator and provides fire event counts
FIRE ALARM
Illuminates the yellow Off Normal Event LED
Displays
FIRE ALARM
Displays information on how to react to the event in the Instructional Text Area
Latching events must be corrected and a Reset performed to clear the alarm state from the N16
Initiating Device Activation
Produces a steady audible tone
Flashes the
FIRE ALARM
Displays a type code that indicates the type of fire alarm being generated
Latches the control panel in alarm (condition must be corrected and a reset performed to clear the alarm state from the panel)
Activates the general alarm zone (Z000)
Displays
FIRE ALARM
Sends an alarm message to the graphic display, remote annunciators, history buffer, and installed printers
Initiates any control-by-event actions
Starts timers such as Silence Inhibit and Auto Silence
Sends an alarm message to the proprietary receiver via the network, if applicable. If the panel is not networked, the CGW-MB will be
directly connected to the fire panel and send the alarm message to the proprietary receiver via the CGW-MB
NOTE: If the alarm event is initiated by a device with a waterflow type Code, the control panel will disable the Signal Silence key and the Auto
Silence Timer.
Responding to a fire alarm event:
The Informational Text Area on the screen will indicate step by step how to acknowledge and silence the event.
Tap on the
ACKNOWLEDGE
the acknowledged event. A
events have been acknowledged, the blue highlight indicator will move from the
Tap on the
SILENCE
silenced and all silenceable outputs will turn off.
Investigate and correct the condition that activated the Fire Alarm.
Once the N16 has been silenced the blue highlight indicator will move from the
Tap the
RESET
N16 Instruction Manual P/N LS10239-000NF-E:A 04/20/2021
and specific device information in the Events List
in the status banner on the control panel, along with information specific to the device
FIRE ALARM
1
Step 1 Acknowledge each event. This is secondary text to explain what acknowledging an event means and who should do it.
FIRE ALARM
UNACKNOWLEDGED FIRE ALARMS (1)
FIRE ALARM
CO ALARM
MONITOR
SUPERVISORY
TROUBLE
DISABLE
OTHER
SIGNALS
SILENCED
Figure 3 Fire Alarm Screen
touchpoint located in the Header Bar, which will be highlighted in blue. A check mark will appear next to
will need to be tapped for each Fire Event. Block Acknowledge is not available. Once all the
CKNOWLEDGE
touchpoint located in the Header Bar. The
touchpoint located in the Header Bar to return the N16 to normal operations.
Ack
Silence
Third Floor, Storage Room
Zone Z001 (Z001)
ACKNOWLEDGE
icon in the Alert Bar will illuminate yellow once the N16 has
SILENCE
SILENCE
Thu 2/22/20
1:38:06PM
Reset
Thu 02/22/20
1:45:57 PM
NO25L01M026
touchpoint to the
touchpoint to the
RESET
Operations
touchpoint.
SILENCE
touchpoint.
61