Network Interface And Options; Setting Up An Opc Client Application - Honeywell Vertex M Technical Handbook

Continuous gas monitor
Hide thumbs Also See for Vertex M:
Table of Contents

Advertisement

Vertex M
24-Point Continuous Monitor
TM
A.2 OLE for Process Control (OPC)
Interface
The primary method of alarm and fault annunciation
used by the Vertex M Gas analyzer relies on the Allen
Bradley SLC500 PLC system installed in the base
enclosure using optional fieldbusses or contact closure.
A secondary method for annunciation and data
access is available via the Ethernet network port on
the Vertex M Data Acquisition System using OPC.
Concentration data as well as alarm and fault status
are available through this interface. The OPC drivers
are automatically initialized at startup of the application,
enabling the Vertex M to act as an OPC Server. The
user may connect to the Network interface Cards RJ45
Port at the rear of the data Acquisition System See
Section 1.2.7 Data Acquisition Computer
The Vertex M contains 1331 OPC tags as listed in
Table A-3. Tag
Names. Many of these are present for
historical reasons and have low utility for an external
HMI system. The column "recommended for most HMI
systems" is provided to help separate the useful from
the obscure. The number of recommended tags is 317.
CAUTION
OPC via Ethernet is not recommended for the primary
safety system notification.
CAUTION
Tunnel OPC communication outside the Vertex M rack
using secure software such as KepWare OPC Connectiv-
ity Suite or Matrikon OPC Tunneller. OPC communication
among Microsoft Windows computers is not highly resistant
to cyberattack.
Appendix A - Network Interface and Options
A.2.1 Setting Up an OPC Client Application
To request data from Vertex M your OPC Client
application will need to include the following information.
More information on OPC and client application is
available at www.opcfoundation.org.
Table A-2. Additional OPC Client information
Server
Type
Server
Computer
Name or
Address
(rear).
Access
Path
Update
Rate
Item
F-3
Honeywell.VertexOPCServerDA.1
Local
Enter the Computer Name of the
Vertex M Data acquisition PC
from Settings, Control Panel,
System, Network Identification.
Typically: Vertex M_291-####,
with the # being the 4 digit serial
number.
Project name. You can leave this
blank. If you do specify a name,
use the name of the open project.
A period in seconds.
Tag name. Whether to specify
an item depends on the client
application.