3.2.15

Offline Configuration

Overview
Offline Configuration refers to configuring a device when the device is not physically present or
communicating with the application. This process enables the user to create and save a
configuration for a device, even when the device is not there physically. Later when the device
becomes available with live communication, the same configuration can be downloaded to the
device. This feature enables the user to save on device commissioning time and even helps the
user to replicate the configuration in multiplicity of devices with lesser efforts. Currently, FDC does
not support creating offline configuration. However, it supports importing of offline configuration
from FDM R310 or later versions. The configurations thus imported can be downloaded to the
device from FDC.
The following are the tasks that the user needs to perform for importing offline configuration in
FDC application software and then downloading it to the device.
Create offline configuration template in FDM
Save the configuration in FDM in FDM format.
Import the offline configuration in FDC
Download the offline configuration to the device
Note: For details on creating and using offline configuration, refer to section Offline configuration
in FDM User's Guide.
Importing offline configuration
Using this feature the user can import offline configuration template. The offline configuration
template has to be created in FDM and saved in FDM format. Copy the .fdm files into the storage
location of the FDC.
To import an offline configuration, perform the following steps.
1. On the FDC homepage, tap Offline Configuration > Select.
The Offline Configurations page appears.
2. Tap Options > Import.
The Select a File dialog box appears.
3. Navigate to the location where the offline configuration template is stored.
4. Select the required offline configuration template from the list.
5. Double-tap and the offline configuration template is imported.
A success message appears.
Note: In case if the offline configuration template is already imported, an overwrite message
appears.
6. Tap OK to return to the Offline Configurations page. The device details appear on the
bottom of the page.