Table 5 - Advanced Configuration parameters, cont'd
Bold = Configurable
Services cont.
The Tamper Alarm feature provides a warning if more than a specified
number of attempts or actual configuration changes are made, whether
write protected or not, when Tamper Alarm is Enabled. The warning
stays active until the specified latency period has elapsed after the
Primary Master reads the corresponding status byte. Examples of
attempted configuration changes: moving the Write-Protect jumper,
entering a wrong password.
The method allows user to configure the following parameters in the
order as specified below:
1.
2.
3.
When enabled, the "Attempt Counter" will keep track of the number of
times an attempt is made. After the configured "Max Attempts", an
alarm status (non-critical flag) is generated.
Displays the number of device configuration change attempts
made when tamper mode is enabled.
Changing the tamper mode from enable to disable and vice-
versa is also considered as configuration change attempt and
"Attempt Counter" is incremented.
If user configures "Max Allowable Attempts" to a value less
than the current "Attempt Counter " then "Attempt Counter " is
clamped to "Max Allowable Attempts.
0-60 seconds. Tamper latency is the time period for which the tamper
alarm remains set in response of command 48 and reflected as
"Tamper Alarm" Device Status condition.
Maximum number of tamper attempts to be permitted before the
Tamper Alarm is generated.
Reset the Attempt Counter to zero.
Selecting this option will cause a Master Reset of the transmitter, which
is the equivalent to power cycling the device.
Select the Lock state for access by HART configuration tools.
If "Yes" is selected to lock the device, also select "Yes" or "No" to
choose whether or not the lock is "permanent." If the lock is not
permanent, it will be cleared on power cycle or Master Reset of the
device.
If "Yes" is selected to unlock the device, the lock state will be cleared.
Resets all device configuration parameters to their factory defaults and
triggers a soft reset. The User will be prompted to confirm they want to
take this action.
Read and display both Comm and Sensor Model Numbers.
Display Model Number Mismatch non-critical diagnostic.
Provide a Match Model Number command with selections to match
from Comm or match from Sensor, which is only visible or enabled
during a Model Number Mismatch diagnostic.
SLG 700 Series HART Option User's Manual
Bold underline = Method
Tamper Mode
Tamper Latency
Maximum Allowable Attempts
Bold italic = Table or graph
Revision 5