Honeywell SLG 700 User Manual page 80

Smartline level transmitter guided wave radar hart option
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Name (DTM/DD)
URV Set Error - Span
Config Button
LRV Set Error - Zero
Config Button
Surface signal quality
bad
Surface signal strength
bad
Interface signal quality
bad
Interface signal
strength bad
Sensor Configuration
DB RAM Corrupt
Strapping/Linearization
Table Absent
Display Common
Config DB corrupt
Display View Config
DB corrupt
Display Common DB
RAM Corrupt
Display View DB RAM
Corrupt
Adv Diag DB RAM
corrupt
Config Change DB
RAM corrupt
General Config DB
RAM corrupt
Vital Configuration DB
RAM Corrupt
Page 72
Description (Cause)
Set operation using external Span
button was rejected.
Set operation using external Zero
button was rejected.
Surface signal quality is bad.
Surface signal strength is weak
Interface signal quality is bad.
Lower product signal strength is
weak.
RAM copy of Sensor configuration
database block found corrupt.
1. If linearization table is not available
in communication board NVM when
level linearization is enabled
2. If strapping table is not available
when volume calculation type is
Strapping table.
NVM copy of Display general
parameters database block found
corrupt.
NVM copy of Display view/screen
configuration database block found
corrupt.
RAM copy of display general
parameters database block found
corrupt.
RAM copy of display view/screen
configuration database block found
corrupt.
RAM copy of advanced diagnostics
database block found corrupt
RAM copy of configuration history
database block found corrupt.
RAM copy of general configuration
database block found corrupt.
RAM copy of Vital configuration
database block found corrupt
SLG 700 Series HART Option User's Manual
Resolution (Steps to take)
Please check whether the inputs are
valid for the intended operation.
Please check whether the inputs are
valid for the intended operation.
Read the Echo curve and configure
algorithm and DC parameters
accordingly using the DTM.
Read the Echo curve and configure
algorithm and DC parameters
accordingly.
Read the Echo curve and configure
algorithm and DC parameters
accordingly.
Read the Echo curve and configure
algorithm and DC parameters
accordingly.
Power cycle the device
Configure the Linearization table before
level linearization is enabled. Configure
the Strapping table to select Volume
calculation type "Strapping table".
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
common NVM data.
Power cycle the device and re-configure
display configuration if required.
Use clear NVM corrupt method from
host to clear the NVM error.
This method will default the Display
view data.
Power cycle the device and re-configure
display configuration if required.
Power cycle the device and re-configure
display configuration if required.
Power cycle the device and if problem
still persists replace the Communication
module.
Power cycle the device and if problem
still persists replace the Communication
module.
Power cycle the device and if problem
still persists replace the Communication
module.
Power cycle the device and if problem
still persists replace the Communication
module.
Power cycle the device and if problem
still persists replace the Communication
module.
Revision 5