Table 5 - Advanced Configuration parameters, cont'd
Key:
Plain = Read only
Bold = Configurable
Prcs Connector Refle.
Attenuation
Prcs Connector Threshold
Amplitude Tracking
Config. Calib. Offset
Calibration Offset
Reference Plane offset
Proces. Connec. Offset
Config. Attenuation
Vapor Attenuation
Upper Prod. Attenuation
Lower Prod. Attenuation
Table 5 - Advanced Configuration parameters, cont'd
Key:
Plain = Read only
Install Date
NAMUR
Enabled,
Output
Disabled
NAMR Level
Image
Page 28
Bold underline = Method
Correlation Algorithm, cont'd
Increased attenuation results in smaller side lobes of the wave's shape.
If changing the gain does not help try increasing threshold.
This feature enhances the sensor to track levels under dynamic conditions or
when the radar pulse attenuations in the media are not well known. Once the
sensor has locked onto a correct level, it will track the amplitude of the
reflection rather than using the user configured model amplitude
Offset to compensate for a change in geometry at the process connector that
affects the measurement.
Read only. Distance between the reference radar pulse reflection and the
physical reference plane (flange) in the factory.
Read only.
This sets the linear attenuation coefficient (Radar Pulse energy dissipation) of
Vapor.
This sets the linear attenuation coefficient (Radar Pulse energy dissipation) of
Upper Product (For Two Liquids, otherwise this is just Product/Surface
attenuation).
This sets the linear attenuation coefficient (Radar Pulse energy dissipation) of
Lower Product. (For Two Liquids only).
Bold = Configurable
Bold underline = Method
Services
(One time editable) Transmitter installation date in MM/DD/YYYY format.
Note: If install date is not configured default date is shown as 01/01/1972.
Enable or disable the NAMUR output.
Enable: High Saturation current is set to 20.5.
Disable: High Saturation current is set to 20.8.
NAMUR Disabled
SLG 700 Series HART Option User's Manual
Bold italic = Table or graph
Bold italic = Table or graph
NAMUR Enabled
Revision 5