Diagnostics
10.3 Safety messages for SINAMICS S120
Remedy
F30650
Response
Acknowledgment
Explanation
Remedy
10-788
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) - - 10.2015 Edition
Carry out a POWER ON (power off/on) for all components.
-- Re--commission the Safety Integrated function and carry out a
POWER ON.
-- Upgrade the Motor Module/Hydraulic Module software.
-- Contact the Hotline.
-- Replace the Motor Module/Hydraulic Module.
SI P2: Acceptance test required
OFF2
IMMEDIATELY (POWER ON)
The "Safety Integrated" function on monitoring channel 2 requires an
acceptance test.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, interpret as decimal)
130:
Safety parameters for monitoring channel 2 not available.
1000:
Reference and actual checksum on monitoring channel 2 are not
identical (boot).
--
As a result of the changed sampling time of the current controller
(p0115[0]) the clock cycle time for Safety Integrated Basic Func-
tions (r9880) was adapted
--
Safety parameters set offline and loaded to the Control Unit.
--
A download was made to SINAMICS whose firmware version of
monitoring channel 2 did not correspond to the latest version
release. The request to switch off the DRIVE--CLiQ component
A1007 was present after the download.
--
At least one checksum--checked piece of data is defective.
2000:
Reference and actual checksum on monitoring channel 2 not
identical (commissioning mode).
--
Reference checksum incorrectly entered for monitoring channel 2
(p9899 not equal to r9898).
2003:
Acceptance test is required as a safety parameter has been
changed.
2005:
The safety logbook has identified that safety checksums have been
changed. An acceptance test is required.
3003:
An acceptance test is required, as one of the safety parameters
referred to the hardware has been changed.
9999:
Subsequent response of another safety fault that occurred when
powering up, which requires an acceptance test.
For fault value = 130:
-- Carry out safety commissioning routine.
For fault value = 1000:
-- Check the cycle time for the Safety Integrated basic functions
(r9880) and adapt the set checksum (p9899).
-- Repeat safety commissioning.
-- Switch off the drive device and DRIVE--CLiQ components and then
switch on again. If A30650 remains active, then download again.
-- Replace the memory card or the Control Unit.