ACH550-01 User's Manual
Input power (mains) connection
Input power (mains) connection specifications
Voltage (U
Prospective
short-circuit
current
(IEC 629)
Frequency
Imbalance
Fundamental
power factor
(cos phi
)
1
Cable
temperature
rating
Technical data
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
)
208/220/230/240 V AC 3-phase (or 1-phase) -
1
-15%...+10% for 230 V AC units
380/400/415/440/460/480 V AC 3-phase
-15%...+10% for 400 V AC units
Maximum allowed prospective short-circuit
current in the supply is 100 kA in a second
providing that the mains cable of the drive is
protected with appropriate fuses. US: 100 000
AIC
48...63 Hz
Max. ±3% of nominal phase-to-phase input
voltage
0.98 (at nominal load)
90 °C (194 °F) rating minimum