ABB ACH550-UH-011A-6 User Manual page 128

Table of Contents

Advertisement

ACH550-01 User's Manual
Note: The drive starts only if possible protection functions (Run enable or Start enable 1 and
2) are activated from I/O or disabled with parameters.
Application macros and wiring
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Hand control
1
SCR
Signal cable shield (screen)
2
AI1
Not used
3 AGND Analogue input circuit common
4
10V
Reference voltage +10 V DC
5
AI2
Not used
6 AGND Analogue input circuit common
7
AO1
Output frequency: 0(4)...20 mA
8
AO2
Output current: 0(4)...20 mA
9 AGND Analogue output circuit common
10
24V
Auxiliary voltage output +24 V DC
11
GND
Common for DI return signals
12 DCOM Digital input common for all
13
DI1
Not used
14
DI2
Not used
15
DI3
Not used
16
DI4
Not used
17
DI5
Not used
18
DI6
Not used
19 RO1C
Relay output 1 (par. 1401)
20 RO1A
Default operation
Ready => 19 connected to 21
21 RO1B
22 RO2C
Relay output 2 (par. 1402)
23 RO2A
Default operation
Running => 22 connected to 24
24 RO2B
25 RO3C
Relay output 3 (par. 1403)
26 RO3A
Default operation
Fault (-1) => 25 connected to 27
27 RO3B
123

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550-01Ach550

Table of Contents