ABB ACH550-UH-011A-6 User Manual page 244

Table of Contents

Advertisement

ACH550-01 User's Manual
Code Description
2603 IR COMP VOLT
Sets the IR compensation voltage used for 0 Hz.
• Requires parameter 9904
• Keep IR compensation as low as possible to prevent overheating.
• Typical IR compensation values are:
380...480 V drives
P
(kW)
N
IR comp (V)
• When enabled, IR compensation provides an extra voltage boost to
the motor at low speeds. Use IR compensation, for example, in
applications that require a high breakaway torque.
P 2603
2604 IR COMP FREQ
Sets the frequency at which IR compensation is 0 V (in % of motor
frequency).
2605 U/F RATIO
Selects the form for the U/f (voltage to frequency) ratio below field
weakening point.
1 =
– Preferred for constant torque applications.
LINEAR
2 =
SQUARED
(
is more silent for most operating frequencies.)
SQUARED
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
MOTOR CTRL MODE
3
7.5
15
21
18
15
Motor
voltage
A
B
P 2604
– Preferred for centrifugal pump and fan applications.
Range
0...100 V
= 3 (
SCALAR
37
132
10
4
A = IR compensated
B = No compensation
f (Hz)
0...100%
1=LINEAR, 2=SQUARED
:
).
FREQ
239