Group 29: MAINTENANCE TRIG
This group defines usage levels and trigger points. When usage
reaches the set trigger point, a notice displayed on the control
panel (operator keypad) signals that maintenance is due.
Code Description
2901 COOLING FAN TRIG
Sets the trigger point for the drive's cooling fan counter.
• Value is compared to parameter 2902 value.
0.0 – Disables the trigger.
2902 COOLING FAN ACT
Defines the actual value of the drive's cooling fan counter.
• When parameter 2901 has been set to a non-zero value, the counter
starts.
• When the actual value of the counter exceeds the value defined by
parameter 2901, a maintenance notice is displayed on the panel.
0.0 – Resets the parameter.
2903 REVOLUTION TRIG
Sets the trigger point for the motor's accumulated revolutions counter.
• Value is compared to parameter 2904 value.
0 – Disables the trigger.
2904 REVOLUTION ACT
Defines the actual value of the motor's accumulated revolutions
counter.
• When parameter 2903 has been set to a non-zero value, the counter
starts.
• When the actual value of the counter exceeds the value defined by
parameter 2903, a maintenance notice is displayed on the panel.
0 – Resets the parameter.
2905 RUN TIME TRIG
Sets the trigger point for the drive's run time counter.
• Value is compared to parameter 2906 value.
0.0 – Disables the trigger.
2906 RUN TIME ACT
• When parameter 2905 has been set to a non-zero value, the counter
starts.
• When the actual value of the counter exceeds the value defined by
parameter 2905, a maintenance notice is displayed on the panel.
Defines the actual value of the drive's run time counter.
0.0 – Resets the parameter.
242
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
ACH550-01 User's Manual
Range
0.0...6553.5 kh
0.0...6553.5 kh
0...65535 Mrev
0...6553 Mrev
0.0...6553.5 kh
0.0...6553.5 kh