ABB ACH550-UH-011A-6 User Manual page 284

Table of Contents

Advertisement

ACH550-01 User's Manual
Code Description
4003 DERIVATION TIME
Defines the derivation time of the PID controller.
• You can add the derivative of the error to the PID controller output.
The derivative is the error value's rate of change. For example, if the
process error value changes linearly, the derivative is a constant
added to the PID controller output.
• The error-derivative is filtered with a 1-pole filter. The time constant of
the filter is defined by parameter 4004
0.0 – Disables the error-derivative part of the PID controller output.
0.1...10.0 – Derivation time (seconds).
PID output
4004 PID DERIV FILTER
Defines the filter time constant for the error-derivative part of the PID
controller output.
• Before being added to the PID controller output, the error-derivative is
filtered with a 1-pole filter.
• Increasing the filter time smooths the error-derivative, reducing noise.
0.0 – Disables the error-derivative filter.
0.1...10.0 – Filter time constant (seconds).
4005 ERROR VALUE INV
Selects either a normal or inverted relationship between the feedback
signal and the drive speed.
0 =
– Normal, a decrease in feedback signal increases drive speed.
NO
Error = Ref - Fbk.
1 =
– Inverted, a decrease in feedback signal decreases drive
YES
speed. Error = Fbk - Ref.
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Process error value
Error
100%
0%
D-part of the controller output
Gain
P 4001
P 4003
Range
0.0...10.0 s
.
PID DERIV FILTER
t
t
0.0...10.0 s
0=NO, 1=YES