Input power (mains) cable
Dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
Note: The cable must be less than the maximum limit defined by
the terminal size. Check the maximum wire size according to the
table in section
page 408.
The following table gives copper and aluminium cable types for
different load currents. These recommendations apply only for
the conditions listed at the top of the table.
Based on:
• EN 60204-1 and IEC 60364-5-2
• PVC insulation
• 30 °C (86 °F) ambient temperature
• 70 °C (158 °F) surface temperature
• cables with concentric copper shield
• not more than nine cables laid on cable
ladder side by side.
Max
Cu
load
cable
current
2
A
mm
14
3x1.5
20
3x2.5
27
3x4
34
3x6
47
3x10
62
3x16
79
3x25
98
3x35
119
3x50
153
3x70
406
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Input power and motor connection terminals
IEC
Max
Al cable
load
current
A
mm
61
3x25
75
3x35
91
3x50
117
3x70
143
3x95
165
3x120
191
3x150
218
3x185
257
3x240
274
3x
(3x50)
ACH550-01 User's Manual
NEC
Based on:
• NEC Table 310-16 for copper
wires
• 90 °C (194 °F) wire insulation
• 40 °C (104 °F) ambient
temperature
• not more than three current-
carrying conductors in
raceway or cable, or earth
(directly buried)
• copper cables with
concentric copper shield.
Max load
current
2
A
22.8
27.3
36.4
50.1
68.3
86.5
100
118
137
155
1
on
Cu wire size
AWG/kcmil
14
12
10
8
6
4
3
2
1
1/0
Technical data