Code Description
4024 PID SLEEP DELAY
Sets the time delay for the PID sleep function – a motor speed/
frequency below 4023
enables the PID sleep function (stopping the drive).
• See 4023
4025 WAKE-UP DEV
Defines the wake-up deviation – a deviation from the setpoint greater
than this value, for at least the time period 4026
the PID controller.
• Parameters 4006 and 4007 define the units and scale.
• Parameter 4005 = 0,
Wake-up level = Setpoint - Wake-up deviation.
• Parameter 4005 = 1,
Wake-up level = Setpoint + Wake-up deviation.
• Wake-up level can be above or below setpoint.
See the figure:
• C = Wake-up level when parameter 4005 = 1
• D = Wake-up level when parameter 4005 = 0
• E = Feedback is above wake-up level and lasts longer than 4026
-
WAKE
UP DELAY
• F = Feedback is below wake-up level and lasts longer than 4026
-
WAKE
UP DELAY
4026 WAKE-UP DELAY
Defines the wake-up delay – a deviation from the setpoint greater than
4025
-
WAKE
UP DEV
controller.
• See 4023
288
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
PID SLEEP LEVEL
above.
PID SLEEP LEVEL
– PID function wakes up.
– PID function wakes up.
P 4025
Setpoint
P 4025
, for at least this time period, restarts the PID
above.
PID SLEEP LEVEL
ACH550-01 User's Manual
Range
0.0...3600 s
for at least this time period
unit and scale defined
by par. 4106 and 4107
-
WAKE
E
P 4026
P 4026
F
0...60 s
Parameter listing and descriptions
, restarts
UP DELAY
C
D
t