ABB ACH550-UH-011A-6 User Manual page 384

Table of Contents

Advertisement

ACH550-01 User's Manual
Fault
Fault name in
code
the panel
1012
PAR PFA IO
1013
PAR PFA IO
1014
PAR PFA IO
1015
RESERVED
1016
PAR USER LOAD
C
-
UNKNOWN DRIVE
: ACH550
TYPE
SUPPORTED
:
DRIVES
X
Diagnostics and maintenance
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
recommended corrective action
1
IO configuration is not complete – not
enough relays are parameterized for PFA.
Or, a conflict exists between group 14,
parameter 8117
parameter 8118
2
IO configuration is not complete – the actual
number of PFA motors (parameter 8127
) does not match the PFA motors in
MOTORS
group 14 and parameter 8118
.
INTERV
3
IO configuration is not complete – the drive
is unable to allocate a digital input (interlock)
for each PFA motor (parameters 8120
and 8127
INTERLOCKS
Not used.
Parameter values for the user load curve are
inconsistent. Check that the following
conditions are met:
• 3704
LOAD FREQ
3710
LOAD FREQ
3713
LOAD FREQ
• 3705
LOAD TORQ LOW
1.
HIGH
• 3708
LOAD TORQ LOW
2.
HIGH
• 3711
LOAD TORQ LOW
3.
HIGH
• 3714
LOAD TORQ LOW
4.
HIGH
• 3717
LOAD TORQ LOW
5.
HIGH
Wrong type of panel, i.e. panel that supports
drive X but not the ACH550, has been
connected to the ACH550.
Description and
NR OF AUX MOT
AUTOCHNG INTERV
AUTOCHNG
).
MOTORS
1 < 3707
LOAD FREQ
3 <
4 < 3716
LOAD FREQ
1 < 3706
2 < 3709
3 < 3712
4 < 3715
5 < 3718
and
.
2 <
5.
LOAD TORQ
LOAD TORQ
LOAD TORQ
LOAD TORQ
LOAD TORQ
379