ABB ACH550-UH-011A-6 User Manual page 198

Table of Contents

Advertisement

ACH550-01 User's Manual
Code Description
1106 REF2 SELECT
Selects the signal source for external reference
0...17 – Same as for parameter 1103
19 =
1
PID
OUT
40: PROCESS PID SET 1
20...21 – Same as for parameter 1103
19=
1
PID
1...17
20...21
1107 REF2 MIN
Sets the minimum for external reference 2.
• The minimum analogue input signal (in volts or amperes)
corresponds to
• Parameter 1301
analogue input signal.
• This parameter sets the minimum frequency reference.
• The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque.
1108 REF2 MAX
Sets the maximum for external reference 2.
• The maximum analogue input signal (in volts or amperes)
corresponds to
• Parameter 1302
analogue input signal.
• This parameter sets the maximum frequency reference.
• The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque.
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
– The reference is taken from the
and
Group 41: PROCESS PID SET
2
LIMIT
REF
SELECT
2
in %.
REF
MIN
1 or 1304
MINIMUM AI
2
in %.
REF
MAX
1 or 1305
MAXIMUM AI
Range
0...17, 19...21
2.
REF
1
REF
SELECT
1 output. See
PID
1
.
REF
SELECT
(1107, 1108)
MAX
(1107, 1108)
MIN
0...100%
(0...600% for torque)
2 sets the minimum
MINIMUM AI
0...100%
(0...600% for torque)
2 sets the maximum
MAXIMUM AI
Group
2.
If PFA is used
PFA
193