ACH550-01 User's Manual
1
Not available if PID is activated
2
Disable/enable with parameters 1601 and 1608
Note: The drive starts only if possible protection functions (Run enable or Start enable 1 and
2) are activated from I/O or disabled with parameters.
Application macros and wiring
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Floating point
1
SCR
Signal cable shield (screen)
2
AI1
Not used
3 AGND Analogue input circuit common
4
10V
Reference voltage +10 V DC
5
AI2
Not used
6 AGND Analogue input circuit common
7
AO1
Output frequency: 0(4)...20 mA
8
AO2
Output current: 0(4)...20 mA
9 AGND Analogue output circuit common
10
24V
Auxiliary voltage output +24 V DC
11
GND
Common for DI return signals
12 DCOM Digital input common for all
13
DI1
Start/Stop: Activation starts the drive
14
DI2
Run enable: Deactivation stops the drive
15
DI3
Constant speed 1 (par. 1202)
16
DI4
Start enable 1: Deactivation stops the drive
17
DI5
Reference up: Activation increases the reference
18
DI6
Reference down: Activation decreases the reference
19 RO1C
Relay output 1 (par. 1401)
20 RO1A
Default operation
Started => 19 connected to 21
21 RO1B
22 RO2C
Relay output 2 (par. 1402)
23 RO2A
Default operation
Running => 22 connected to 24
24 RO2B
25 RO3C
Relay output 3 (par. 1403)
26 RO3A
Default operation
Fault (-1) => 25 connected to 27
27 RO3B