Group 32: SUPERVISION
This group defines supervision for up to three signals from
Group 01: OPERATING
parameter and energises a relay output if the parameter passes
a defined limit. Use
relay and whether the relay activates when the signal is too low
or too high.
Code Description
3201 SUPERV 1 PARAM
Selects the first supervised parameter.
• Must be a parameter number from
• 101...178 – Supervises parameter 0101...0178.
• If the supervised parameter passes a limit, a relay output is
energised.
• The supervision limits are defined in this group.
• The relay outputs are defined in
(definition also specifies which supervision limit is monitored).
LO ≤ HI
Operating data supervision using relay outputs, when LO ≤ HI. See the
figure on page 254.
• Case A = Parameter 1401
etc.) value is
if the supervised signal exceeds a given limit. The relay remains
active until the supervised value drops below the low limit.
• Case B = Parameter 1401
etc.) value is
when/if the supervised signal falls below a given limit. The relay
remains active until the supervised value rises above the high limit.
LO > HI
Operating data supervision using relay outputs, when LO>HI. See the
figure on page 254.
The lowest limit (
supervised parameter goes above the highest limit (
that limit the active limit. That limit remains active until the supervised
parameter goes below the lowest limit (
active.
• Case A = Parameter 1401
etc.) value is
energised. It is energised whenever the supervised parameter goes
above the active limit.
• Case B = Parameter 1401
etc.) value is
energised. It is de-energised whenever the supervised parameter
goes below the active limit.
Parameter listing and descriptions
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
DATA. Supervision monitors a specified
Group 14: RELAY OUTPUTS
Group 14: RELAY OUTPUTS
RELAY OUTPUT
1
or
SUPRV
OVER
SUPRV
RELAY OUTPUT
1
or
SUPRV
UNDER
SUPRV
3203) is active initially, and remains active until the
HI
RELAY OUTPUT
1
or
SUPRV
OVER
SUPRV
RELAY OUTPUT
1
or
SUPRV
UNDER
SUPRV
to define the
Range
101...178
Group 01: OPERATING
1 (or 1402
RELAY OUTPUT
2
. Use for monitoring when/
OVER
1 (or 1402
RELAY OUTPUT
2
. Use for monitoring
UNDER
3202), making
LO
3203), making that limit
HI
1 (or 1402
RELAY OUTPUT
2
. Initially the relay is de-
OVER
1 (or 1402
RELAY OUTPUT
2
. Initially the relay is
UNDER
DATA.
2,
2,
2,
2,
253