9.3.3.2 Scenarios for Connecting the ECC800 Collector

9.3.3.2.1 Commissioning Southbound Devices of ECC800

For details, see commissioning chapter in ECC800 Data Center Controller User
Manual.

9.3.3.2.2 Setting and Adding the ECC800 Collector

The requirements for ECC800 WebUI login are as follows.
Computer operating system: Support Windows 7 and later versions
Browser: IE11 and later versions; Firefox and later versions; Chrome and later
versions

?.1. Setting NetEco Parameters

When the smart module can be connected to the NetEco, perform the following
steps to configure parameters.
Procedure
Step 1 Apply for a fixed IP address to the equipment room network administrator.
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800 WebUI.
Table 9-10 IP parameters
Path
System
Settings >
System
Parameter
s >
Monitor
Module IP
> WAN_1
Step 3 Set NetEco communications parameters on the ECC800 WebUI.
Issue 03 (2022-12-15)
Parameter
IP
Subnet
mask
Default
gateway
Copyright © Huawei Digital Power Technologies Co., Ltd.
9 Commissioning Core Components
Default
Setting Value
Value
192.168.1.1
Set this parameter based on the IP
0
address assigned by the network
administrator.
255.255.25
Set this parameter based on the
5.0
subnet mask assigned by the network
administrator.
192.168.1.1
Set this parameter based on the
default gateway address assigned by
the network administrator.
89